SF6 circuit breakers · voltage class

110 kV SF6 circuit breakers: dead-tank and live-tank

For 110 kV networks we supply two SF6 circuit breakers for a highest operating voltage of 145 kV: the dead-tank 3AP1 DT (rated current 3,150 A, breaking current 40 kA, built-in current transformers) and the live-tank 3AP1 FG (4,000 A, 40 kA). Both series come in three-pole and single-pole versions, with a spring-operated mechanism and an interrupter designed for minimum operating energy, for service from −60 to +55 °C.

Highest operating voltage145kV Rated current3,150–4,000A Breaking current40kA Temperature−60 to +55 °C
SF6 circuit breakers in the air-insulated switchyard of a substation

Key facts

  • Network class 110 kV → highest operating voltage of the apparatus 145 kV.
  • Dead-tank 3AP1 DT · 145 kV: 3,150 A, 40 kA, built-in toroidal current transformers on the bushings.
  • Live-tank 3AP1 FG · 145 kV: 4,000 A, 40 kA, interrupter on an insulating column.
  • Both series: three-pole and single-pole versions, spring-operated mechanism, service from −60 to +55 °C.

Two series for 110 kV

Dead-tank or live-tank for a 110 kV network

145 kV breakers for 110 kV networks: ratings and design features from the series data tables
ParameterDead-tank 3AP1 DT145 kVLive-tank 3AP1 FG145 kV
Highest operating voltagekV145145
Rated currentA3,1504,000
Rated breaking currentkA4040
Location of the interrupterin an earthed tankon an insulating column at line potential
Built-in current transformersyes — compact toroidal CTs on the bushingsno
Insulating and arc-quenching mediummixture of SF6 and a fluorocarbon (pure SF6 on request)SF6
Versionsthree-pole and single-polethree-pole and single-pole
Operating mechanismspring-operatedspring-operated
Operating temperature−60 to +55 °C−60 to +55 °C

The live-tank breaker is more compact and lighter; the dead-tank breaker suits sites that need built-in current transformers and high seismic withstand.

How to select a 110 kV circuit breaker

A 110 kV circuit breaker is selected on the basis of the bay data; the simplest way to send them is an enquiry data sheet, on which we base the technical and commercial proposal. The values obtained are then checked against the series ratings in the section “Dead-tank or live-tank for a 110 kV network”. Where there is no room for an air-insulated switchyard, 110 kV GIS is considered instead of outdoor breakers.

Selecting a breaker for a 110 kV network: which parameters to determine
ParameterHow to determine it
Voltagefor the 110 kV voltage class the highest operating voltage is 126 kV (GOST R 52565-2006); the next higher value in the IEC 62271-1 series is 145 kV
Rated currentnot lower than the highest continuous current of the bay, including post-fault conditions
Breaking currentnot lower than the calculated short-circuit current at the point of installation
Climateby the lowest site temperature; for frosts down to −60 °C, the UKhL1 and KhL1 climatic versions to GOST 15150-69
Current transformersnumber of cores, ratios and accuracy classes: metering — 0.2S or 0.5S, protection — 5P or 10P (GOST 7746-2015); the dead-tank 3AP1 DT has built-in current transformers, while separate ones are installed for the live-tank 3AP1 FG
Pole operationa mechanism per pole is needed for single-phase tripping and single-phase auto-reclosing

Applications

Where they are installed

  • air-insulated switchyards of 110 kV substations
  • 110 kV distribution networks: line and transformer bays
  • substations of industrial plants and power stations
  • switchyard refurbishment replacing oil and air-blast breakers

Industries

Installation supervision and acceptance tests

Before energisation a 110 kV circuit breaker undergoes acceptance tests to the Russian Electrical Installation Code (PUE, 7th edition, clause 1.8.21), and the results are compared with its passport and the manufacturer’s limits. We carry out installation supervision of newly installed equipment under a separate contract, including together with supply.

Acceptance tests of an SF6 circuit breaker to PUE clause 1.8.21
CheckRequirement
insulation resistance of secondary circuits and control coil windingsto clause 1.8.37
high-voltage withstand test of the insulationat power frequency; may be omitted if the breaker was filled with SF6 at the factory and is not to be opened during its service life
resistance of the main circuit — of the whole pole and of each breakwithin the manufacturer’s limits
minimum operating voltageno more than 0.85 of rated voltage with a DC supply to the mechanism, 0.7 with an AC supply
grading capacitorsto clause 1.8.30, if fitted; capacitance within the manufacturer’s limits
breaker characteristics, e.g. closing and opening timesscope as set out in the manufacturer’s instructions, results within the passport data
repeated operations3–5 closings and openings, 2–3 operating cycles of each type
gas tightnessthe leak detector shows no leaks at the rated SF6 pressure
SF6 moisture contentdew point not higher than −50 °C
built-in current transformersto clause 1.8.17

The tests are carried out by our own high-voltage test laboratory: Rostechnadzor certificate No. 9834 of 20 December 2024 entitles it to perform acceptance tests and measurements of electrical equipment rated up to 750 kV, including SF6 circuit breakers. After commissioning the breaker is maintained by our high-voltage equipment service.

Service and testing

Documents

Catalogue “High-voltage equipment”

PDF

PDF
Enquiry data sheet: circuit breaker

DOCX · fill in online

DOCX

Questions and answers

Why a 145 kV breaker for a 110 kV network?

Under GOST R 52565-2006 the highest operating voltage for the 110 kV voltage class is 126 kV. The nearest values in the IEC 62271-1 series of rated voltages are 123 and 145 kV; 123 kV is below 126 kV, so a 145 kV apparatus is chosen for a 110 kV network. The dead-tank 3AP1 DT and the live-tank 3AP1 FG are built for this voltage.

Which dead-tank breaker is needed for a 110 kV network?

The 3AP1 DT for a highest operating voltage of 145 kV: rated current 3,150 A, <a class="term-link" href="../glossary/breaking-current/index.html" title="What is the breaking current of a circuit breaker">breaking current</a> 40 kA, built-in toroidal current transformers.

Which live-tank breaker is needed for a 110 kV network?

The 3AP1 FG for a highest operating voltage of 145 kV: rated current 4,000 A, <a class="term-link" href="../glossary/breaking-current/index.html" title="What is the breaking current of a circuit breaker">breaking current</a> 40 kA.

How does a 110 kV dead-tank breaker differ from a live-tank one?

In a dead-tank breaker the interrupter sits in an earthed tank that also houses the <a class="term-link" href="../glossary/current-transformer/index.html" title="What is a current transformer">current transformers</a>; in a live-tank breaker it sits on an insulating column at line potential. The live-tank breaker is more compact and lighter; the dead-tank breaker suits sites that need built-in CTs and high seismic withstand.

Do 110 kV breakers operate at −60 °C?

Yes, both series operate from −60 to +55 °C. The dead-tank 3AP1 DT uses a mixture of SF6 and a fluorocarbon for cold climates; pure SF6 on request.

Which tests does a 110 kV circuit breaker undergo before energisation?

Acceptance tests to PUE clause 1.8.21: insulation resistance of secondary circuits, a high-voltage withstand test of the insulation (it may be omitted for a breaker filled with SF6 at the factory and not opened during its service life), main circuit resistance, minimum operating voltage, the characteristics listed in the manufacturer’s instructions, repeated operations, gas tightness, SF6 moisture and the built-in current transformers. Our test laboratory is registered with Rostechnadzor: certificate No. 9834 of 20 December 2024.

Can installation supervision be ordered together with the breaker supply?

Yes. Installation supervision of newly installed equipment is carried out under a separate contract and can go together with supply; the tests are performed by our own test laboratory. After that the breaker is maintained by our service centre: maintenance without pumping out the SF6 on request or after 12 years, complex repair at the works on request or after 25 years.

Expert in charge

High-voltage equipment

Manufacturers' names and designations are used to identify the equipment we supply and service. Trademarks belong to their respective owners. Energy Management LLC is an independent engineering and service company.

CallSend a request
Service requestRequest a quotationData sheet