What is a live-tank circuit breaker
A live-tank circuit breaker is a high-voltage SF6 circuit breaker whose interrupter sits on a support insulating column at line potential. The interrupter and the column are filled with SF6 and form a single gas volume; the operating mechanism is at the base of the column. It is lighter and cheaper than a dead-tank breaker but has no built-in current transformers.
Key facts
- The interrupter sits on a support insulating column at line potential.
- Current transformers are separate apparatus.
- 3AP1 FG and 3AP2 FI series for 72.5–550 kV.
- For 110 kV networks: 145 kV, up to 4,000 A, 40 kA.
- Lighter and cheaper than a dead-tank breaker, needs less SF6.
How it is built
A pole consists of a support column — a porcelain or composite insulator with an insulating rod inside — and an interrupter on top with terminals for the busbar connection. The spring or hydraulic mechanism sits on the frame at the bottom and drives the contacts through the rod. For 330 kV and above, two or more interrupters per pole are connected in series with grading capacitors to share the voltage evenly between the breaks.
Series and ratings
The 3AP1 FG and 3AP2 FI live-tank breakers are built for 72.5–550 kV. For 110 kV networks (rated voltage 145 kV) the 3AP1 FG has a rated current of up to 4,000 A, a breaking current of 40 kA and one interrupter per pole. Standard operating temperature −55 to +55 °C; for −60 °C heaters or gas mixtures are used.
Where it is used
Air-insulated 110–750 kV switchyards in temperate climates; substations where current transformers are installed separately. Live-tank breakers are lighter, occupy less area, need less SF6 and are easier to transport, which makes them the most common breakers at grid substations.
How it differs from a dead-tank breaker
In a dead-tank breaker the interrupter is inside an earthed tank and the current transformers are built into the bushings; it copes better with seismic loads and low temperatures. In a live-tank breaker the interrupter is at line potential, the current transformers are separate and the centre of gravity is high, but the mass, the gas volume and the price are lower.
Maintenance
The same as for dead-tank breakers: SF6 density monitoring, mechanism inspection, checks of operating characteristics and main-circuit resistance. Work on the interrupter requires the feeder to be switched off and earthed, because the interrupter is live.
Questions and answers
Why does a live-tank breaker have several interrupters per pole?
At 330 kV and above one break is not enough: two or more interrupters per pole are connected in series, and grading capacitors share the voltage evenly between them. For a 110 kV network one interrupter per pole is sufficient.
Where are live-tank breakers used?
In air-insulated 110–750 kV switchyards in temperate climates where current transformers are installed separately. This is the most common breaker type at grid substations: lighter, smaller in footprint, with less SF6 and easier to transport.
How is a live-tank breaker maintained?
SF6 density is monitored, the mechanism is checked by the number of operations, contact timing and synchronism and main-circuit resistance are measured. Work on the interrupter starts only after the feeder is switched off and earthed, because the interrupter is live. This work is done by our high-voltage equipment service.