What is a dead-tank circuit breaker
A dead-tank circuit breaker is a high-voltage SF6 circuit breaker whose interrupter is housed in an earthed metal tank filled with SF6 gas; the live parts are brought out through bushings that carry built-in current transformers. Cold-climate versions operate down to −60 °C.
Key facts
- The interrupter sits in an earthed steel tank filled with SF6.
- Current transformers are built into the bushings — no separate CTs needed.
- 3AP1 DT and 3AP2 DT series for 72.5–550 kV.
- For 110 kV networks: 145 kV, 3,150 A, 40 kA.
- The cold-climate version operates down to −60 °C.
How it is built
Each pole is a steel tank at earth potential; inside it, in SF6, sits the interrupter with its moving and fixed contacts. Current enters and leaves through two bushings, on which ring-type current transformers are mounted, so separate instrument transformers are not needed at the substation. The operating mechanism is spring or hydraulic, common to the three poles or per pole. For −60 °C the tank is filled with an SF6–CF4 mixture or equipped with heaters.
Series and ratings
The 3AP1 DT and 3AP2 DT dead-tank breakers are built for 72.5–550 kV. For 110 kV networks (rated voltage 145 kV) the 3AP1 DT has a rated current of 3,150 A, a breaking current of 40 kA and built-in toroidal current transformers on the bushings. Versions for 220, 330 and 500 kV use series-connected interrupters with grading capacitors. Operating temperature −60 to +55 °C; the assembly plant can build up to 350 breakers a year.
Where it is used
Air-insulated 110–500 kV switchyards in cold climates, heavily polluted or seismically active areas; substations where compact busbar layout matters and separate current transformers are not required. The earthed tank simplifies maintenance and improves safety: the mechanism and bushings can be serviced without climbing to live parts.
How it differs from a live-tank breaker
In a live-tank breaker the interrupter sits on an insulating column at line potential; it is lighter and cheaper but has no built-in current transformers and copes worse with seismic loads and low temperatures. The dead-tank breaker is heavier and needs more SF6, but reduces the number of apparatus at the substation and simplifies the layout.
Maintenance
SF6 density monitoring, mechanism inspection by number of operations, checks of contact timing and synchronism, main-circuit resistance measurement. Interrupter overhaul is scheduled by the accumulated short-circuit interruption duty.
Questions and answers
How does a dead-tank breaker differ from a live-tank one?
In a dead-tank breaker the interrupter is inside an earthed tank and the current transformers are built into the bushings; in a live-tank breaker the interrupter sits on an insulating column at line potential and the CTs are separate. The dead-tank type copes better with earthquakes and cold, the live-tank type is lighter, cheaper and needs less SF6.
Does a dead-tank breaker work at −60 °C?
Yes, in the cold-climate version: to keep SF6 from liquefying, the tank is filled with an SF6–CF4 (tetrafluoromethane) mixture or fitted with heaters. The 3AP DT series is rated for −60 to +55 °C.
Which current transformers are built into a dead-tank breaker?
Ring-type (toroidal) current transformers are mounted on the bushings. Each bushing may carry several cores: metering cores for billing and protection cores for relays. This removes separate current transformers and their foundations from the substation.