What is air-insulated switchgear (AIS)

AIS is air-insulated switchgear: circuit breakers, disconnectors, current and voltage transformers, surge arresters and busbars are installed outdoors on gantries and support structures. The insulating medium is air, so the phase clearances are large and the condition of the apparatus depends on the climate and pollution.

Key facts

  • Stands for air-insulated switchgear (ORU in Russian).
  • The insulating medium is air, so phase clearances are large.
  • Includes breakers, disconnectors, current and voltage transformers, surge arresters.
  • Cheaper than GIS in equipment but needs 25–30 times more space.
  • Apparatus condition depends on climate, ice and pollution.

How it is built

AIS feeders are assembled from free-standing apparatus: an SF6 circuit breaker — dead-tank or live-tank, disconnectors with earthing blades, current transformers (built-in on dead-tank breakers), voltage transformers, surge arresters. Busbars are flexible conductors on gantries or rigid tubular bars. Phase-to-phase and phase-to-earth clearances depend on the voltage class: metres at 110 kV, tens of metres at 500 kV.

Where it is used

Substations of grid companies and power stations where land is available and there are no strict requirements for protection from the environment. For cold climates, polluted atmospheres and seismic areas, dead-tank breakers with heaters or gas mixtures are chosen.

How it differs from GIS

AIS is cheaper in equipment and simpler to repair apparatus by apparatus, but occupies 25–30 times more space, needs regular insulator cleaning and is exposed to ice, wind and salt pollution. GIS is compact, lasts more than 50 years and is independent of the environment, but requires on-site testing and SF6 monitoring. The choice depends on the cost of land, the climate and reliability requirements.

Maintenance and testing

Periodic inspections, thermal imaging of contacts, insulation and main-circuit resistance measurement, breaker characteristic checks, tests of current and voltage transformers. The company’s service centre supports AIS breakers over their whole life and the test laboratory performs tests up to 750 kV.

Questions and answers

What does AIS stand for?

AIS stands for air-insulated switchgear (ORU in Russian): electrical apparatus installed outdoors on gantries and support structures. The alternatives are indoor switchgear and GIS. AIS is the most common switchgear type at 110–500 kV substations.

AIS or GIS for a new substation?

The choice depends on land cost, climate and reliability requirements. AIS is cheaper in equipment and easier to repair apparatus by apparatus; GIS is compact, independent of weather and pollution and lasts more than 50 years. Cities, industrial sites and polluted areas usually get GIS.

Which breakers are used in 110–500 kV AIS?

SF6 breakers: live-tank in temperate climates, dead-tank in cold, seismic and polluted areas. Dead-tank breakers with built-in current transformers reduce the number of apparatus in the switchyard. See 110–500 kV SF6 circuit breakers to choose a version.