What is GIS (gas-insulated switchgear)

GIS is gas-insulated switchgear: circuit breakers, disconnectors, earthing switches, instrument transformers and busbars are housed in sealed earthed enclosures filled with SF6 gas. It takes 25–30 times less space than air-insulated switchgear, is independent of weather and pollution and lasts more than 50 years.

Key facts

  • Stands for gas-insulated switchgear (KRUE in Russian documents).
  • Bay classes: 145, 245 and 330/550 kV, short-circuit current 40–63 kA.
  • Takes 25–30 times less space than air-insulated switchgear.
  • Service life over 50 years with SF6 leakage of no more than 0.1 % a year.
  • After erection every bay must pass a high-voltage withstand test.

The name

GIS stands for gas-insulated switchgear; in Russian documents it is called KRUE (complete SF6-insulated switchgear). “Complete” means the switchgear is delivered assembled from ready modules and tested at the factory; at the substation the bays are only joined together and connected to transformers and lines.

How it is built

A GIS bay is assembled from modules: the circuit breaker, disconnectors and earthing switches, current and voltage transformers, busbars, cable or overhead-line terminations. All live parts rest on support insulators inside sealed earthed aluminium-alloy enclosures filled with SF6 gas, whose dielectric strength is about 2.5 times that of air. The enclosure is divided into gas compartments, each with a density monitor providing alarm and lock-out. The circuit breaker has a motor-spring operating mechanism with three-phase or single-phase control.

Voltage classes and ratings

Three classes of bays for 110, 220, 330 and 500 kV networks: 145 kV (short-circuit current 40 kA, rated current 3,150 A), 245 kV (50 kA, 3,150 A) and 330/550 kV (63 kA, 4,000 A; busbars up to 6,300 A). Bay width is 800 mm at 145 kV (1,200 mm with single-phase control), 1,500 mm at 245 kV and 3,600 mm at 550 kV. Operating temperature −30 to +40 °C, 50/60 Hz.

Where it is used

At substations where there is no room for air-insulated switchgear or protection from the environment is required: in cities, on industrial sites, at LNG plants and power stations, and in polluted areas. GIS is installed in buildings or in prefabricated modules, which protects the apparatus from the climate and simplifies maintenance.

How it differs from air-insulated switchgear

It takes 25–30 times less space, does not depend on the weather or on pollution and lasts more than 50 years with SF6 leakage of no more than 0.1 % a year; the first visual inspection is after nine years. It is extended by adding bays without interrupting the existing substation. The price is a mandatory high-voltage test on site and gas density monitoring throughout the service life.

Testing and operation

After erection every bay is tested at raised voltage with partial discharge measurement to detect particles left inside the enclosure during assembly. In service the SF6 density, the operating mechanisms and the contact wear by the number of operations are monitored. The team’s reference: 1,920 sets of GIS equipment at the 220 kV TsRP substation in Krasnoyarsk.

Questions and answers

What does GIS stand for?

GIS stands for gas-insulated switchgear; Russian documents call it KRUE. It is “complete” because the bays are assembled from factory-tested modules and are only joined together and connected at the substation.

How does GIS differ from AIS?

Air-insulated switchgear is built from free-standing apparatus in the open air, while GIS consists of modules in earthed SF6-filled enclosures. GIS takes 25–30 times less space, does not depend on weather or pollution and lasts over 50 years, but needs on-site testing and SF6 density monitoring.

How long does GIS last and when is the first inspection due?

The service life exceeds 50 years with SF6 leakage of no more than 0.1 % a year per gas compartment. The first visual inspection is due after nine years in service; in between, gas density, operating mechanisms and contact wear by the number of operations are monitored.

Related terms