High-voltage equipment · series

Gas-insulated switchgear 145, 245 and 330–550 kV

Gas-insulated switchgear for 110, 220, 330 and 500 kV networks: bays for 145, 245 and 330/550 kV with a short-circuit current of 40–63 kA and a busbar current up to 6,300 A. SF6 leakage is no more than 0.1% a year, service life is over 50 years and the first visual inspection falls due after 9 years. GIS takes 25–30 times less space than an air-insulated switchyard and can be extended without interrupting operation.

Voltage145 · 245 · 550kV Short-circuit currentup to 63kA Busbar currentup to 6300A Leakage≤ 0.1% a year Service life50+years
245 kV GIS bay on the assembly stand

Key facts

  • Three bay classes: 145 kV (40 kA, 3,150 A), 245 kV (50 kA, 3,150 A), 330/550 kV (63 kA, 4,000 A; busbars 6,300 A).
  • Bay width is 800 mm at 145 kV (1,200 mm with single-phase operation), 1,500 mm at 245 kV and 3,600 mm at 550 kV.
  • SF6 leakage no more than 0.1% a year; service life over 50 years; first visual inspection after 9 years.
  • Motor-spring operating mechanism; frequency 50/60 Hz; operation at temperatures from −30 to +40 °C.
  • Track record: 1,920 sets of GIS equipment at the 220 kV TsRP substation (Rosseti).

Three voltage classes

110 kV → 145 kV bay

Separate page: 110 kV GIS — 145 kV bays

GIS bay 145 kV, 40 kA, 3,150 A: data
ParameterValue
VoltagekV145
FrequencyHz50/60
AC withstand test voltage (1 min, 50 Hz)kV275
Lightning impulse withstand voltage (1.2/50 µs)kV650
Busbar currentA3,150
Feeder currentA3,150
Short-circuit currentkA40
Short-time current (3 s)kA40
Leakage a yearno more than 0.1%
Bay widthmm800 (three-phase operation), 1,200 (single-phase)
Bay weightabout 3 t
Operating mechanismmotor-spring
Ambient temperature°C−30 to +40
Service lifemore than 50 years

220 kV → 245 kV bay

GIS bay 245 kV, 50 kA, 3,150 A: data
ParameterValue
VoltagekV245
FrequencyHz50/60
AC withstand test voltage (1 min, 50 Hz)kV460
Lightning impulse withstand voltage (1.2/50 µs)kV1,050
Busbar currentA3,150
Feeder currentA3,150
Short-circuit currentkA50
Short-time current (3 s)kA50
Leakage a yearno more than 0.1%
Bay widthmm1,500
Bay weightabout 5 t
Operating mechanismmotor-spring
Ambient temperature°C−25 to +40
Service lifemore than 50 years

330 and 500 kV → 330/550 kV bay

GIS bay 330/550 kV, 63 kA, 4,000 A: data
ParameterValue
VoltagekV550
FrequencyHz50/60
AC withstand test voltage (1 min, 50 Hz)kV750
Lightning impulse withstand voltage (1.2/50 µs)kV1,675
Busbar currentA6,300
Feeder currentA4,000
Short-circuit currentkA63
Short-time current (3 s)kA63
Leakage a yearno more than 0.1%
Bay widthmm3,600
Bay weightabout 5 t
Operating mechanismmotor-spring
Ambient temperature°C−25 to +40
Service lifemore than 50 years

Summary table

Compare:
GIS: summary table for the three voltage classes
Parameter145 kV40 kA, 3,150 A245 kV50 kA, 3,150 A330/550 kV63 kA, 4,000 A
VoltagekV145245550
FrequencyHz50/6050/6050/60
AC withstand test voltage (1 min, 50 Hz)kV275460750
Lightning impulse withstand voltage (1.2/50 µs)kV6501,0501,675
Busbar currentA3,1503,1506,300
Feeder currentA3,1503,1504,000
Short-circuit currentkA405063
Short-time current (3 s)kA405063
Leakage a yearno more than 0.1%no more than 0.1%no more than 0.1%
Bay widthmm800 (three-phase operation), 1,200 (single-phase)1,5003,600
Bay weightabout 3 tabout 5 tabout 5 t
Operating mechanismmotor-springmotor-springmotor-spring
Ambient temperature°C−30 to +40−25 to +40−25 to +40
Service lifemore than 50 yearsmore than 50 yearsmore than 50 years

15 advantages of GIS

  1. 01Resistance to environmental exposure
    The live parts and the apparatus sit in sealed earthed enclosures filled with SF6: dust, moisture, salt and precipitation do not affect the insulation.
  2. 02Low electromagnetic emissions
    The earthed metal enclosures screen the field; personnel may be present in the GIS hall continuously.
  3. 03High seismic withstand
    Compact rigid modules on common frames take seismic loads better than the extended structures of air-insulated switchgear.
  4. 04Modular layout
    The bay is assembled from standard modules — circuit breaker, disconnectors, current and voltage transformers, busbars.
  5. 05Extension and refurbishment of air-insulated switchgear without interrupting operation
    New bays are connected to a substation in service without disconnecting consumers.
  6. 06Simple structure and few foundations
    The modules stand on common frames: fewer supports and foundations than in an air-insulated switchyard.
  7. 07Built-in digital control and monitoring systems (partial discharge and voltage presence sensors)
    The sensors are fitted into the enclosures at the works; insulation condition is monitored remotely.
  8. 0825–30 times less area required
    Bay width runs from 800 mm at 145 kV to 3,600 mm at 550 kV, instead of the tens of metres taken by an air-insulated switchyard.
  1. 09Low land costs
    Less area means less land, fencing, roads and lighting.
  2. 10Short design and erection times
    Standard modules and factory assembly cut both the design work and the erection work on site.
  3. 11High availability
    Sealed insulation and factory testing reduce the number of failures and unplanned outages.
  4. 12Low maintenance costs (first visual inspection after 9 years)
    A diagnostic survey and maintenance follow on request or after 12 years, complex repair after 25 years.
  5. 13Personnel safety
    All live parts are enclosed in earthed housings — there are no exposed live parts.
  6. 14Module assembly and testing at the works
    The modules are assembled, filled with SF6 and tested at the works; on site they are joined together and the erected switchgear is tested.
  7. 15Service life more than 50 years
    With SF6 leakage no more than 0.1% a year.
GIS in the switchgear hall
145 kV GIS hall
245 kV GIS bay on the assembly stand
245 kV bay on the assembly stand
GIS bay with its control cabinet
Bay with its control cabinet

Documents

Catalogue “High-voltage equipment”

PDF

PDF
Enquiry data sheet: GIS

DOCX · fill in online

DOCX

Fill in the online enquiry data sheet

Questions and answers

How much space does GIS take?

25–30 times less than an air-insulated switchyard; bay width runs from 800 mm at 145 kV to 3,600 mm at 550 kV.

Which bay is needed for a 110 kV network?

The 145 kV bay: 40 kA, 3,150 A, 800 mm wide with three-phase operation and 1,200 mm with single-phase operation, weighing about 3 t.

Can a substation in service be extended?

Yes: <a class="term-link" href="../glossary/gis/index.html" title="What is GIS (gas-insulated switchgear)">GIS</a> connects to air-insulated switchgear and extends it without interrupting operation.

What is the service life of GIS?

More than 50 years, with SF6 leakage no more than 0.1% a year.

After how many years is the first GIS inspection needed?

For the GIS in our catalogue, the first visual inspection is due after 9 years in service; for equipment from other manufacturers, the intervals are taken from the operating manual. Under the service contract, the preliminary inspection is carried out when the contract is signed, a diagnostic survey and maintenance on request or after 12 years, and complex repair on request or after 25 years.

How is GIS tested after erection?

With an AC withstand test at the installation site using a mobile resonant test system up to 750 kV and partial discharge measurement — carried out by our own test laboratory.