Gas-insulated switchgear 145, 245 and 330–550 kV
Gas-insulated switchgear for 110, 220, 330 and 500 kV networks: bays for 145, 245 and 330/550 kV with a short-circuit current of 40–63 kA and a busbar current up to 6,300 A. SF6 leakage is no more than 0.1% a year, service life is over 50 years and the first visual inspection falls due after 9 years. GIS takes 25–30 times less space than an air-insulated switchyard and can be extended without interrupting operation.

Key facts
- Three bay classes: 145 kV (40 kA, 3,150 A), 245 kV (50 kA, 3,150 A), 330/550 kV (63 kA, 4,000 A; busbars 6,300 A).
- Bay width is 800 mm at 145 kV (1,200 mm with single-phase operation), 1,500 mm at 245 kV and 3,600 mm at 550 kV.
- SF6 leakage no more than 0.1% a year; service life over 50 years; first visual inspection after 9 years.
- Motor-spring operating mechanism; frequency 50/60 Hz; operation at temperatures from −30 to +40 °C.
- Track record: 1,920 sets of GIS equipment at the 220 kV TsRP substation (Rosseti).
Three voltage classes
110 kV → 145 kV bay
Separate page: 110 kV GIS — 145 kV bays
| Parameter | Value |
|---|---|
| VoltagekV | 145 |
| FrequencyHz | 50/60 |
| AC withstand test voltage (1 min, 50 Hz)kV | 275 |
| Lightning impulse withstand voltage (1.2/50 µs)kV | 650 |
| Busbar currentA | 3,150 |
| Feeder currentA | 3,150 |
| Short-circuit currentkA | 40 |
| Short-time current (3 s)kA | 40 |
| Leakage a year | no more than 0.1% |
| Bay widthmm | 800 (three-phase operation), 1,200 (single-phase) |
| Bay weight | about 3 t |
| Operating mechanism | motor-spring |
| Ambient temperature°C | −30 to +40 |
| Service life | more than 50 years |
220 kV → 245 kV bay
| Parameter | Value |
|---|---|
| VoltagekV | 245 |
| FrequencyHz | 50/60 |
| AC withstand test voltage (1 min, 50 Hz)kV | 460 |
| Lightning impulse withstand voltage (1.2/50 µs)kV | 1,050 |
| Busbar currentA | 3,150 |
| Feeder currentA | 3,150 |
| Short-circuit currentkA | 50 |
| Short-time current (3 s)kA | 50 |
| Leakage a year | no more than 0.1% |
| Bay widthmm | 1,500 |
| Bay weight | about 5 t |
| Operating mechanism | motor-spring |
| Ambient temperature°C | −25 to +40 |
| Service life | more than 50 years |
330 and 500 kV → 330/550 kV bay
| Parameter | Value |
|---|---|
| VoltagekV | 550 |
| FrequencyHz | 50/60 |
| AC withstand test voltage (1 min, 50 Hz)kV | 750 |
| Lightning impulse withstand voltage (1.2/50 µs)kV | 1,675 |
| Busbar currentA | 6,300 |
| Feeder currentA | 4,000 |
| Short-circuit currentkA | 63 |
| Short-time current (3 s)kA | 63 |
| Leakage a year | no more than 0.1% |
| Bay widthmm | 3,600 |
| Bay weight | about 5 t |
| Operating mechanism | motor-spring |
| Ambient temperature°C | −25 to +40 |
| Service life | more than 50 years |
Summary table
| Parameter | 145 kV40 kA, 3,150 A | 245 kV50 kA, 3,150 A | 330/550 kV63 kA, 4,000 A |
|---|---|---|---|
| VoltagekV | 145 | 245 | 550 |
| FrequencyHz | 50/60 | 50/60 | 50/60 |
| AC withstand test voltage (1 min, 50 Hz)kV | 275 | 460 | 750 |
| Lightning impulse withstand voltage (1.2/50 µs)kV | 650 | 1,050 | 1,675 |
| Busbar currentA | 3,150 | 3,150 | 6,300 |
| Feeder currentA | 3,150 | 3,150 | 4,000 |
| Short-circuit currentkA | 40 | 50 | 63 |
| Short-time current (3 s)kA | 40 | 50 | 63 |
| Leakage a year | no more than 0.1% | no more than 0.1% | no more than 0.1% |
| Bay widthmm | 800 (three-phase operation), 1,200 (single-phase) | 1,500 | 3,600 |
| Bay weight | about 3 t | about 5 t | about 5 t |
| Operating mechanism | motor-spring | motor-spring | motor-spring |
| Ambient temperature°C | −30 to +40 | −25 to +40 | −25 to +40 |
| Service life | more than 50 years | more than 50 years | more than 50 years |
15 advantages of GIS
01Resistance to environmental exposure
The live parts and the apparatus sit in sealed earthed enclosures filled with SF6: dust, moisture, salt and precipitation do not affect the insulation.02Low electromagnetic emissions
The earthed metal enclosures screen the field; personnel may be present in the GIS hall continuously.03High seismic withstand
Compact rigid modules on common frames take seismic loads better than the extended structures of air-insulated switchgear.04Modular layout
The bay is assembled from standard modules — circuit breaker, disconnectors, current and voltage transformers, busbars.05Extension and refurbishment of air-insulated switchgear without interrupting operation
New bays are connected to a substation in service without disconnecting consumers.06Simple structure and few foundations
The modules stand on common frames: fewer supports and foundations than in an air-insulated switchyard.07Built-in digital control and monitoring systems (partial discharge and voltage presence sensors)
The sensors are fitted into the enclosures at the works; insulation condition is monitored remotely.0825–30 times less area required
Bay width runs from 800 mm at 145 kV to 3,600 mm at 550 kV, instead of the tens of metres taken by an air-insulated switchyard.
09Low land costs
Less area means less land, fencing, roads and lighting.10Short design and erection times
Standard modules and factory assembly cut both the design work and the erection work on site.11High availability
Sealed insulation and factory testing reduce the number of failures and unplanned outages.12Low maintenance costs (first visual inspection after 9 years)
A diagnostic survey and maintenance follow on request or after 12 years, complex repair after 25 years.13Personnel safety
All live parts are enclosed in earthed housings — there are no exposed live parts.14Module assembly and testing at the works
The modules are assembled, filled with SF6 and tested at the works; on site they are joined together and the erected switchgear is tested.15Service life more than 50 years
With SF6 leakage no more than 0.1% a year.
Bay gallery



Related
Documents
Questions and answers
How much space does GIS take?
25–30 times less than an air-insulated switchyard; bay width runs from 800 mm at 145 kV to 3,600 mm at 550 kV.
Which bay is needed for a 110 kV network?
The 145 kV bay: 40 kA, 3,150 A, 800 mm wide with three-phase operation and 1,200 mm with single-phase operation, weighing about 3 t.
Can a substation in service be extended?
Yes: <a class="term-link" href="../glossary/gis/index.html" title="What is GIS (gas-insulated switchgear)">GIS</a> connects to air-insulated switchgear and extends it without interrupting operation.
What is the service life of GIS?
More than 50 years, with SF6 leakage no more than 0.1% a year.
After how many years is the first GIS inspection needed?
For the GIS in our catalogue, the first visual inspection is due after 9 years in service; for equipment from other manufacturers, the intervals are taken from the operating manual. Under the service contract, the preliminary inspection is carried out when the contract is signed, a diagnostic survey and maintenance on request or after 12 years, and complex repair on request or after 25 years.
How is GIS tested after erection?
With an AC withstand test at the installation site using a mobile resonant test system up to 750 kV and partial discharge measurement — carried out by our own test laboratory.
Expert in charge
High-voltage equipmentManufacturers' names and designations are used to identify the equipment we supply and service. Trademarks belong to their respective owners. Energy Management LLC is an independent engineering and service company.