What is a current transformer
A current transformer is an instrument transformer that converts the current of the power circuit into a proportional secondary current, usually 1 or 5 A, for meters, instruments and protection relays. The primary winding is connected in series with the circuit; in dead-tank breakers and GIS it is built in as a ring core on the bushing or inside the enclosure.
Key facts
- Converts the primary current into a standard secondary current of 1 or 5 A.
- Cores: metering (0.2S, 0.5S) and protection (5P, 10P).
- The secondary circuit must never be opened under load.
- Dead-tank breakers and GIS have built-in current transformers.
- After erection polarity, ratio and insulation are checked.
How it is built
A magnetic core with the secondary winding surrounds the conductor rod or busbar, which acts as a single-turn primary. One transformer has several cores: metering cores of accuracy class 0.2S or 0.5S and protection cores of class 5P or 10P, which keep their accuracy at short-circuit currents. The secondary circuit is never opened under load: a dangerous voltage appears across an open winding.
Designs for 110–500 kV
Free-standing — with SF6 or oil-paper insulation on a support insulator. Built-in — ring cores on the bushings of dead-tank breakers and inside GIS enclosures; they need no space at the substation and no separate foundations. Built-in current transformers are what distinguishes a dead-tank breaker from a live-tank one.
Selection parameters
Rated primary current and ratio, accuracy class and number of cores, rated secondary burden, accuracy limit factor for protection, the highest voltage of the class (145, 245, 550 kV) and the thermal short-time current equal to the network short-circuit current.
Testing
After erection the polarity, ratio, insulation resistance and excitation curves of the cores are checked; transformers inside GIS are tested at raised voltage together with the bay. The company’s test laboratory tests current and voltage transformers up to 750 kV on site.
Questions and answers
Why must a CT secondary never be opened?
A current transformer operates close to a short-circuited secondary. If the secondary is opened while primary current flows, the core saturates and a high voltage appears across the terminals, dangerous to people and insulation. Unused secondary windings are therefore short-circuited.
How does a metering core differ from a protection core?
A metering core (classes 0.2S and 0.5S) is accurate across the operating current range and serves billing. A protection core (classes 5P and 10P) stays accurate at multiples of rated current during short circuits so that relays identify the fault correctly.
How are current transformers tested after erection?
Polarity and ratio are checked, excitation curves of the cores are recorded and insulation resistance is measured. Transformers inside GIS are tested at raised voltage together with the bay. This work is done by our test laboratory up to 750 kV.