What is the rated (highest) voltage of equipment

The rated (highest) voltage is the upper limit of voltage at which apparatus operates continuously. For a 110 kV network it is 145 kV to IEC (126 kV to GOST), for 220 kV — 245 kV (252 kV), for 330 kV — 363 kV, for 500 kV — 550 kV (525 kV). This is why a circuit breaker or GIS bay “for 145 kV” is intended for a 110 kV class network.

Key facts

  • The upper voltage limit for continuous operation of the apparatus.
  • 110 kV network → 145 kV to IEC (126 kV to GOST).
  • 220 kV → 245 kV, 330 kV → 363 kV, 500 kV → 550 kV.
  • Insulation test voltages are tied to it.
  • “145 kV · 3,150 A · 40 kA” means apparatus for a 110 kV network.

Network class and apparatus voltage

The network voltage class — 110, 220, 330, 500 kV — is the nominal voltage around which the network operates with deviations. Apparatus must withstand the voltage with a margin for regulation and overvoltages, so its rating is set by the highest operating voltage. In international practice (IEC 62271) the series is 72.5, 145, 245, 362/363, 550 kV; in Russian standards 126, 252, 363, 525 kV. Imported and localised apparatus is designated by the IEC series, hence a “145 kV breaker” at a 110 kV substation.

Test voltages

Insulation levels are tied to the rated voltage: the one-minute power-frequency withstand voltage and the lightning impulse. Typical values for the 145 kV class are 275 kV and 650 kV, for 245 kV — 460 and 1,050 kV, for 550 kV — 620–740 and 1,550 kV. On site GIS is tested at a voltage below the factory value, usually 80 % of it, with partial discharge measurement.

How to read the ratings

“3AP1 DT · 145 kV · 3,150 A · 40 kA” means a dead-tank breaker for a 110 kV network with a rated voltage of 145 kV, a rated current of 3,150 A and a breaking current of 40 kA. A GIS bay “245 kV · 50 kA” is intended for a 220 kV network.

Where it appears on this site

All high-voltage equipment pages: 72.5–550 kV breakers, 145, 245 and 330/550 kV GIS bays, the selection page by voltage class 110 · 220 · 330 · 500 kV, and the test laboratory’s tests up to 750 kV.

Questions and answers

Why is a 145 kV breaker installed in a 110 kV network?

Because 110 kV is the nominal network voltage, while the apparatus must continuously withstand the network’s highest operating voltage including regulation. The IEC series gives 145 kV for the 110 kV class, GOST gives 126 kV. Imported and localised apparatus is designated to IEC.

How does nominal voltage differ from rated voltage?

Nominal voltage is the network class it operates around: 110, 220, 330 or 500 kV. Rated (highest) voltage is the limit the voltage may reach in normal operation and for which the insulation is designed: 145, 245, 363 and 550 kV to IEC.

Which test voltages belong to the 145 kV class?

Typical insulation levels for the 145 kV class are a 275 kV one-minute power-frequency withstand voltage and a 650 kV lightning impulse. On site, GIS is tested at about 80 % of the factory power-frequency voltage.