Gas turbine or gas engine genset: what to choose for on-site power generation
In brief. Gas engine gensets are more economical up to a few megawatts and with a variable load: they have a higher electrical efficiency (over 41 %) and lower gas pressure requirements. Gas turbines are justified from tens of megawatts, where steam is needed and availability must be high. Microturbines occupy the niche from 100 kW to 2 MW, where low emissions and infrequent maintenance matter.
How to compare
The comparison rests on five features: unit output and load range, electrical and overall efficiency, fuel requirements, service life and the maintenance interval, emissions and noise. For on-site generation a sixth feature also matters — how much heat the plant needs and in what form: steam or hot water.
Output and load range
gas engine gensets deliver from hundreds of kilowatts to several megawatts per unit; a power plant is assembled from several machines and copes well with a variable load. Microturbines cover 110–1,966 kW. Gas turbines on this site are rated 5–62 MW and work best at a steady load close to the rating.
Efficiency and heat
The electrical efficiency of a gas engine genset is over 41 %, and the overall efficiency with heat recovery reaches 87 %. Gas turbines of 5–62 MW have a simple-cycle efficiency of 30.1–41.1 %, and their hot exhaust yields a great deal of steam; microturbines in simple cycle produce up to 7.7 t/h of steam, and with a recuperator fuel consumption is almost halved.
Fuel
Gas engine gensets run on natural, associated petroleum, landfill and industrial gas and on biogas at low pressure. The 2100 series of microturbines also runs on waste gases from production. Gas turbines need gas at a higher pressure and with a stable composition.
Service life and maintenance
A gas engine genset is serviced more often, and the interval to major overhaul is set by the manufacturer. Microturbines run for long periods without maintenance: the 135 series has accumulated more than 130,000 hours without remarks. Gas turbines are serviced by operating hours: inspections, medium and major overhaul.
Emissions and noise
Microturbines: NOx ≤ 25 ppm, noise ≤ 85 dB(A). Gas turbines with DLE: 25 ppm NOx. Gas engine gensets: NOx ≤ 500 mg/Nm³.
Summary table
| Feature | Gas engine gensets | Microturbines | Gas turbines |
|---|---|---|---|
| Unit output | hundreds of kW to several MW | 110–1,966 kW | 5–62 MW |
| Electrical efficiency | over 41 % | — | 30.1–41.1 % (simple cycle) |
| Overall efficiency | up to 87 % | — | — |
| Heat | hot water | steam up to 7.7 t/h | exhaust 478–581 °C, steam |
| Fuel | natural, associated, landfill and industrial gas, biogas | natural and associated gas; waste gases (2100) | natural gas |
| Life to major overhaul | set by the manufacturer | over 130,000 hours accumulated by the 135 series | by operating hours, inspections |
| NOx | ≤ 500 mg/Nm³ | ≤ 25 ppm | 25 ppm (DLE) |
When to choose which
Up to a few megawatts with a variable load — gas engine gensets. From 100 kW to 2 MW with strict requirements for emissions, noise and infrequent maintenance — microturbines. From tens of megawatts, where steam is needed and availability must be high — gas turbines.
Terms used in the article
Questions and answers
Can a microturbine and a gas engine genset be combined?
What matters more when choosing — efficiency or service life?
Sources and standards
The gas turbine and microturbine figures are taken from the sections of this website. DLE stands for Dry Low Emission.