What is a resonant test system
A resonant test is an AC high-voltage test in which the inductance of the test set and the capacitance of the test object form an oscillating circuit. At the resonant frequency the circuit itself generates the high voltage and the supply only covers the losses — tens of times less power than a test transformer needs. This is how GIS and cables are tested up to 750 kV on site.
Key facts
- The test set’s reactor and the object’s capacitance form an oscillating circuit.
- At resonance the voltage on the object is 40–100 times the supply voltage.
- The set is fed from the ordinary site supply.
- Test frequency is usually 20–300 Hz.
- Used for GIS, circuit breakers, transformers and cables.
How it works
The test object — GIS bays, a breaker, a bus duct, a cable — is a capacitance. The test set adds a reactor to it; a frequency converter finds the frequency at which the inductive and capacitive reactances are equal, usually in the 20–300 Hz range. At resonance the voltage on the object is many times the supply voltage (circuit quality factor 40–100), so the set is fed from the ordinary site network. The test voltage is raised smoothly, held for the specified time and partial discharges are measured at the same time.
Types of test sets
Variable frequency — fixed inductance, the frequency is tuned to the capacitance of the object; the lightest and most common mobile systems. Variable inductance — an adjustable core gap at the power frequency of 50 Hz. Modules are connected in series or in parallel to obtain the required voltage or current.
The company’s equipment
Two mobile resonant AC test systems: WRV 3.6/680 M and WRV 1.5/680 G — test voltage up to 750 kV, supply from the site network, transported by road. With them the test laboratory tests GIS, SF6 breakers, disconnectors, earthing switches and transformers of 110–750 kV on the erection site.
How it differs from other methods
A test transformer for 500 kV GIS would need hundreds of kilovolt-amperes and would not fit on site; DC tests are not representative for SF6 and cable insulation and may damage it. The resonant method gives an AC voltage close to the operating waveform with light equipment.
Questions and answers
Why is GIS not tested with an ordinary test transformer?
For 500 kV GIS a test transformer would need hundreds of kilovolt-amperes and would not fit on site. A resonant set draws only the loss power from the supply, weighs several times less and travels by road.
Can SF6 insulation be tested with DC voltage?
It is not recommended: the field distribution under DC differs from service conditions, defects show up differently and charges on spacers may damage the insulation. GIS is therefore tested with AC voltage close to the operating waveform, which resonant sets provide.
Which resonant systems does Energy Management use?
Two mobile resonant AC systems, WRV 3.6/680 M and WRV 1.5/680 G, with test voltages up to 750 kV. With them the test laboratory tests 110–750 kV GIS, SF6 breakers, disconnectors and transformers on site.