What is boil-off gas
Boil-off gas is the part of liquefied natural gas that evaporates in tanks, pipelines and tankers because of heat ingress from outside: usually 0.05–0.1 % of the storage volume per day. It cannot be vented to the atmosphere, so boil-off gas is compressed and returned to the liquefaction process, sent to the fuel gas system or re-liquefied.
Key facts
- Evaporates because heat enters tanks, pipelines and tankers.
- Usually 0.05–0.1 % of the storage volume per day.
- Must not be vented — the gas is compressed and used.
- Compressors handle gas down to −160 °C at suction.
- Anti-surge protection of the compressors is mandatory.
Where it comes from
The insulation of tanks and pipelines is not perfect: heat penetrates through the walls, the gas is stirred during filling and loading, and the warm tank walls of a tanker evaporate part of the cargo during loading. Evaporation keeps the tank pressure within narrow limits; without gas removal the pressure would rise until the relief valves opened.
Boil-off gas compressors
Centrifugal or reciprocating machines handling cold gas down to −160 °C at suction: cryogenic casing and rotor materials, special seals, warm-up at shutdowns. The compressed gas goes to the fuel gas system of the power plant’s gas turbines, back to the refrigeration cycle or to booster compressors for re-liquefaction. Capacity is controlled by tank pressure; anti-surge protection is mandatory.
Where it appears on this site
Four boil-off gas compressors at Yamal LNG were supplied, erected and are serviced by the team; at Arctic LNG 2 the boil-off and feed gas compressors were erected and commissioned. Service and anti-surge control of centrifugal compressors to API 617.
Questions and answers
Why can boil-off gas not be vented?
It is methane — a flammable gas with a strong greenhouse effect — and venting it also means losing product. Boil-off gas is therefore compressed and returned to liquefaction, sent to the plant’s fuel gas system or re-liquefied.
How much gas evaporates in an LNG tank?
Usually 0.05–0.1 % of the storage volume per day, depending on insulation and tank size. During tanker loading evaporation rises sharply: the warm tank walls evaporate part of the cargo and the boil-off gas compressors run at full load.
How do boil-off gas compressors differ from ordinary ones?
They handle cold gas down to −160 °C at suction, so the casing and rotor are made of cryogenic materials, with special seals and warm-up at shutdowns. Capacity is controlled by tank pressure — see API 617 centrifugal compressors.