What is anti-surge control

Anti-surge control is a control loop of a centrifugal or axial compressor that, from the measured flow, pressures and speed, calculates the position of the operating point relative to the surge line and opens the recycle valve before the compressor goes into surge. It is implemented within the unit control system or as a separate controller.

Key facts

  • The control line sits about 10 % in flow away from the surge line.
  • The controller calculates reduced flow from pressures, differential and speed.
  • The anti-surge valve opens within 1–2 seconds.
  • The actual surge line is recorded during site tests.
  • Implemented in the unit control system or as a separate controller on a Russian platform.

How it works

On the compressor map a surge line and a control line with about a 10 % flow margin are drawn. From the differential pressure at the flow element, the suction and discharge pressures and the speed, the controller calculates the reduced flow and the distance to the control line. As the point approaches, it opens the anti-surge valve — a fast-acting control valve on the recycle from discharge to suction through a cooler; on a sudden flow drop a step opening is triggered. On shutdown the valve opens in advance.

System components

Flow sensors (an orifice or nozzle), pressure and temperature sensors at suction and discharge, a speed sensor, a controller with the algorithm and a fast control valve with a positioner and an opening time of 1–2 s. Multi-section machines and parallel compressors have separate loops per section and load-sharing coordination.

Tuning on site

The actual surge line is recorded during tests: the flow is reduced gradually until signs of instability appear at several speeds, then the control line is built and the valve dynamics are checked. Tuning from the datasheet map alone is not enough — a real machine after repair, on a different gas and temperature, behaves differently.

Where it appears on this site

Design of new systems, tuning of existing ones and upgrade of obsolete ones for Kobelco, Hanwha, Siemens Energy, Dresser-Rand, MHI and Howden compressors; implementation within the unit control system or as a separate controller on the Russian Ezan platform; verification of algorithms on a digital model of the compressor; linked with compressor service — inspections, seals, bearings by one team.

Questions and answers

Why is an anti-surge valve needed if speed control exists?

Speed changes slowly because of rotor and driver inertia, while on a sudden flow drop or an emergency stop the compressor would surge within fractions of a second. A fast recycle valve opening in 1–2 seconds returns gas to suction and keeps the operating point in the stable zone.

Can an imported anti-surge controller be replaced with a Russian one?

Yes. The algorithms are transferred to a Russian control platform — within the unit control system or as a separate controller — verified on a digital model of the compressor and then tuned on site to the actual surge line. See anti-surge control and compressor protection and migration to a Russian control platform.

When should anti-surge settings be checked?

After flow-path repairs and seal replacement, when gas composition or operating modes change, after sensor or valve replacement and whenever signs of surge appear. Settings taken from the datasheet map must always be verified on site, because a real machine behaves differently.